RCUPS-SYS-SMTSBC1-MIB DEFINITIONS ::= BEGIN IMPORTS MODULE-IDENTITY, OBJECT-TYPE, Integer32 FROM SNMPv2-SMI MODULE-COMPLIANCE, OBJECT-GROUP FROM SNMPv2-CONF rcUpsSystems, Uint32Milli, Int32Milli, Int16, Uint16, Int16Deci, Uint16Deci, Int16Centi, Uint16Centi FROM RCUPS-MIB; rcSmtSbc1MIB MODULE-IDENTITY LAST-UPDATED "202303261537Z" ORGANIZATION "Renuka's Castle" CONTACT-INFO "Martin Edgar Furter Rathod Postal: Renukas Castle 582103 Gadag, Karnataka India E-mail: pen@renukascastle.co.in" DESCRIPTION "The MIB module to describe additional data of Uninterruptible Power Supply System SmtSbc1." REVISION "202303261537Z" DESCRIPTION "initial" ::= { rcUpsSystems 4 } -- data rcSmtSbc1Data OBJECT IDENTIFIER ::= { rcSmtSbc1MIB 1 } rcSmtSbc1DataDcVol OBJECT-TYPE SYNTAX Int32Milli UNITS "V" MAX-ACCESS read-only STATUS current DESCRIPTION "STS - DC voltage" ::= { rcSmtSbc1Data 21 } rcSmtSbc1DataDcmVol1 OBJECT-TYPE SYNTAX Int32Milli UNITS "V" MAX-ACCESS read-only STATUS current DESCRIPTION "DCM1 - DC voltage 1" ::= { rcSmtSbc1Data 27 } rcSmtSbc1DataDcmVol2 OBJECT-TYPE SYNTAX Int32Milli UNITS "V" MAX-ACCESS read-only STATUS current DESCRIPTION "DCM2 - DC voltage 2" ::= { rcSmtSbc1Data 28 } rcSmtSbc1DataInvVolt OBJECT-TYPE SYNTAX Int32Milli UNITS "V" MAX-ACCESS read-only STATUS current DESCRIPTION "STS - Inverter voltage" ::= { rcSmtSbc1Data 13 } rcSmtSbc1DataInvFreq OBJECT-TYPE SYNTAX Int32Milli UNITS "Hz" MAX-ACCESS read-only STATUS current DESCRIPTION "STS - Inverter frequency" ::= { rcSmtSbc1Data 17 } rcSmtSbc1DataInvCurr OBJECT-TYPE SYNTAX Int32Milli UNITS "A" MAX-ACCESS read-only STATUS current DESCRIPTION "STS - Inverter current" ::= { rcSmtSbc1Data 14 } rcSmtSbc1DataInvWatt OBJECT-TYPE SYNTAX Int32Milli UNITS "W" MAX-ACCESS read-only STATUS current DESCRIPTION "STS - Inverter active power" ::= { rcSmtSbc1Data 15 } rcSmtSbc1DataInvVA OBJECT-TYPE SYNTAX Int32Milli UNITS "VA" MAX-ACCESS read-only STATUS current DESCRIPTION "STS - Inverter apparent power" ::= { rcSmtSbc1Data 16 } rcSmtSbc1DataInvPF OBJECT-TYPE SYNTAX Int32Milli UNITS "-" MAX-ACCESS read-only STATUS current DESCRIPTION "STS - Inverter power factor" ::= { rcSmtSbc1Data 18 } rcSmtSbc1DataBypVolt OBJECT-TYPE SYNTAX Int32Milli UNITS "V" MAX-ACCESS read-only STATUS current DESCRIPTION "STS - Bypass mains voltage" ::= { rcSmtSbc1Data 7 } rcSmtSbc1DataBypFreq OBJECT-TYPE SYNTAX Int32Milli UNITS "Hz" MAX-ACCESS read-only STATUS current DESCRIPTION "STS - Bypass mains frequency" ::= { rcSmtSbc1Data 11 } rcSmtSbc1DataBypCurr OBJECT-TYPE SYNTAX Int32Milli UNITS "A" MAX-ACCESS read-only STATUS current DESCRIPTION "STS - Bypass mains current" ::= { rcSmtSbc1Data 8 } rcSmtSbc1DataBypWatt OBJECT-TYPE SYNTAX Int32Milli UNITS "W" MAX-ACCESS read-only STATUS current DESCRIPTION "STS - Bypass mains active power" ::= { rcSmtSbc1Data 9 } rcSmtSbc1DataBypVA OBJECT-TYPE SYNTAX Int32Milli UNITS "VA" MAX-ACCESS read-only STATUS current DESCRIPTION "STS - Bypass mains apparent power" ::= { rcSmtSbc1Data 10 } rcSmtSbc1DataBypPF OBJECT-TYPE SYNTAX Int32Milli UNITS "-" MAX-ACCESS read-only STATUS current DESCRIPTION "STS - Bypass mains Power factor" ::= { rcSmtSbc1Data 12 } rcSmtSbc1DataOutVolt OBJECT-TYPE SYNTAX Int32Milli UNITS "V" MAX-ACCESS read-only STATUS current DESCRIPTION "STS - Output voltage" ::= { rcSmtSbc1Data 1 } rcSmtSbc1DataOutFreq OBJECT-TYPE SYNTAX Int32Milli UNITS "Hz" MAX-ACCESS read-only STATUS current DESCRIPTION "STS - Output frequency" ::= { rcSmtSbc1Data 5 } rcSmtSbc1DataOutCurr OBJECT-TYPE SYNTAX Int32Milli UNITS "A" MAX-ACCESS read-only STATUS current DESCRIPTION "STS - Output current" ::= { rcSmtSbc1Data 2 } rcSmtSbc1DataOutWh OBJECT-TYPE SYNTAX Int32Milli UNITS "kWh" MAX-ACCESS read-only STATUS current DESCRIPTION "STS - Output kWh" ::= { rcSmtSbc1Data 24 } rcSmtSbc1DataOutWatt OBJECT-TYPE SYNTAX Int32Milli UNITS "W" MAX-ACCESS read-only STATUS current DESCRIPTION "STS - Active power" ::= { rcSmtSbc1Data 3 } rcSmtSbc1DataOutVA OBJECT-TYPE SYNTAX Int32Milli UNITS "VA" MAX-ACCESS read-only STATUS current DESCRIPTION "STS - Apparent power" ::= { rcSmtSbc1Data 4 } rcSmtSbc1DataOutPF OBJECT-TYPE SYNTAX Int32Milli UNITS "-" MAX-ACCESS read-only STATUS current DESCRIPTION "STS - Power factor" ::= { rcSmtSbc1Data 6 } rcSmtSbc1DataSysLoadPerc OBJECT-TYPE SYNTAX Int32Milli UNITS "%" MAX-ACCESS read-only STATUS current DESCRIPTION "STS - System load percentage" ::= { rcSmtSbc1Data 23 } rcSmtSbc1DataSysFanPct OBJECT-TYPE SYNTAX Int32Milli UNITS "%" MAX-ACCESS read-only STATUS current DESCRIPTION "STS - Fan duty cycle" ::= { rcSmtSbc1Data 26 } rcSmtSbc1DataSysTemp OBJECT-TYPE SYNTAX Int32Milli UNITS "K" MAX-ACCESS read-only STATUS current DESCRIPTION "STS - Temperature" ::= { rcSmtSbc1Data 22 } -- -- CONFORMANCE -- rcSmtSbc1Conformance OBJECT IDENTIFIER ::= { rcSmtSbc1MIB 255 } rcSmtSbc1Groups OBJECT IDENTIFIER ::= { rcSmtSbc1Conformance 1 } rcSmtSbc1GroupData OBJECT-GROUP OBJECTS { rcSmtSbc1DataDcVol, rcSmtSbc1DataDcmVol1, rcSmtSbc1DataDcmVol2, rcSmtSbc1DataInvVolt, rcSmtSbc1DataInvFreq, rcSmtSbc1DataInvCurr, rcSmtSbc1DataInvWatt, rcSmtSbc1DataInvVA, rcSmtSbc1DataInvPF, rcSmtSbc1DataBypVolt, rcSmtSbc1DataBypFreq, rcSmtSbc1DataBypCurr, rcSmtSbc1DataBypWatt, rcSmtSbc1DataBypVA, rcSmtSbc1DataBypPF, rcSmtSbc1DataOutVolt, rcSmtSbc1DataOutFreq, rcSmtSbc1DataOutCurr, rcSmtSbc1DataOutWh, rcSmtSbc1DataOutWatt, rcSmtSbc1DataOutVA, rcSmtSbc1DataOutPF, rcSmtSbc1DataSysLoadPerc, rcSmtSbc1DataSysFanPct, rcSmtSbc1DataSysTemp } STATUS current DESCRIPTION "all data." ::= { rcSmtSbc1Groups 1 } rcSmtSbc1Compliances OBJECT IDENTIFIER ::= { rcSmtSbc1Conformance 2 } rcSmtSbc1DataCompliance MODULE-COMPLIANCE STATUS current DESCRIPTION "The compliance statement for UPS alarm definitions." MODULE -- this module MANDATORY-GROUPS { rcSmtSbc1GroupData } ::= { rcSmtSbc1Compliances 1 } -- END